SPECIAL SECTION | Motors & Drives
NEMA Premium 4 Motor Efficiency Regulations Roll Out in June 2027
A guide to understanding and preparing for the coming regulations.
Jeff Goldberg | Nidec Motor Corporation/U.S. MOTORS
New regulations from the U.S. Department of Energy (DOE) take effect in June, impacting motor manufacturers, pump manufacturers and the pump industry overall. Motor manufacturers will be the first to be affected by the new rule, which requires electric motors of certain sizes to meet National Electrical Manufacturers Association (NEMA) Premium 4 efficiency levels. The new standard impacts motors from 100 to 250 horsepower (hp), 2 pole through 8 pole and 600 volt and lower.
Motors manufactured on or after June 1, 2027, must meet the new requirement. However, pump OEMs and pump end users can continue to purchase NEMA Premium motors until they are no longer available from motor manufacturers. Some in the industry are stocking up on their current motors in order to have more time to adjust to the new motor rule.
Planning for the new DOE motor efficiency standards now will help plant managers, facility managers, engineers and project managers make the electrical equipment upgrades needed to power the new NEMA Premium 4 motors.
Why Focus on 100 to 250 Horsepower Motors?
The Energy Policy Act from the 1990s requires DOE to conduct intermittent reviews and repeatedly raise the standards on energy efficiency levels. Targeting electric motors is prudent, as motors are generally responsible for about 40% of power consumption worldwide.
The 100 to 250 hp range is the sweet spot, where the efficiency gain can be achieved with available technology and where the energy savings are large enough to justify the higher motor cost. Below 100 hp, the energy savings realized from moving from NEMA Premium efficiency to NEMA Premium 4 efficiency are much smaller.
Above 250 hp, motors tend to be custom engineered, application specific and produced in lower volume. They would be more likely to require a substantial redesign to maintain their performance levels while meeting the new efficiency levels. For many alternating current induction motors in the 100 to 250 hp band, NEMA Premium 4 efficiency can be achieved by adding additional active material, improving rotor and stator designs and reducing losses.
Reduction in Motor Losses
The reduction in motor losses resulting from the redesign to achieve NEMA Premium 4 efficiency levels is significant. For example, for a 100 hp motor, electrical losses (energy converted to heat, instead of used to perform work) are reduced by 17% (Image 1).
The change in efficiency appears to be just a small incremental gain (Image 2), but the real savings come from the reduction in motor losses. In addition to saving energy, the motors run cooler, extending motor life.
To increase motor efficiency to NEMA Premium 4 levels, additional higher grade active materials are needed, affecting the motor cost (Image 3). The motor stator’s stack length will be increased and possibly also the stator lamination’s diameter. While motor manufacturers are striving to make the NEMA Premium 4 motors drop-in replacements for NEMA 3, in some cases, this could potentially require a jump to the next frame size.

| IMAGE 1: 100 hp loss reduction formula (Images courtesy of Nidec Motor Corporation/U.S. MOTORS)
The new NEMA Premium 4 motors will generate more starting torque with less slip than the premium efficient motors they are replacing. Since starting torque is directly related to the starting current, NEMA 4 motors will exhibit an increased inrush current compared to the older premium efficient motors. However, it takes more current to produce higher torque when starting (Image 4). Pump OEMs may want to review their pump configuration tools to ensure the selected pump shaft and coupling can handle the additional torque.

| IMAGE 2: Efficiency comparison for 4 pole weather protected type I (WPI) enclosure
Updated Design & Electrical Standards
Those familiar with NEMA’s letter design standards will notice they have been updated to address the NEMA Premium 4 motor’s higher inrush currents, specified as locked rotor amperage (LRA). The new motor type is called NEMA Design BE. The inrush current of NEMA Premium 4 Design BE is 42% higher than NEMA Premium Design B, at all hp ratings (Image 5).
The National Electrical Code (NEC) 2026 has also been updated for the new Design BE inrush current, increasing the maximum starter overload requirements. The International Electrical Code (IEC) and NEMA have created similar requirements (IEC has design NE and aligns with NEMA’s BE), and IEC starters do exist for the new inrush currents. At the time of this writing, however, no NEMA starters are defined for BE. Currently installed cabling and branch circuits may be undersized for Design BE motors. Fusing and even transformers could potentially have issues. The European Union (EU) market implemented Design NE IEC motors with effectively the same inrush values as NEMA BE in 2023.

| IMAGE 3: Locked rotor amperage comparison for NEMA Premium Design B and Design BE
Additional Installation & Equipment Costs to Support New Motors
While standards groups continue their work to prepare the market for the NEMA Premium 4 changes, it is helpful to be aware that installation costs and components supporting the motor will be affected. It is important to factor these additional costs into planning and bid work.
To manage the inrush current of a NEMA Premium 4 Design BE motor, a variable frequency drive (VFD), part wind, wye-delta or soft starter is required. Lowering the inrush current will reduce starting torque, which is acceptable in variable torque pumping applications. Those applications place little load on the motor at startup, so the motor is not required to develop its full torque when starting.
Powering the motor may also require equipment upgrades. This includes the motor starter and supply lines. Typically, a VFD will not require a change, as the VFD is sized by the full load amps and not the starting amps. However, at this writing, electrical manufacturers have not yet announced Underwriters Laboratories (UL) listed soft starters. In the absence of available soft starters, end users installing a VFD to manage the inrush current need to consider the additional costs of VFD-rated cabling and supporting components to address harmonic currents.

| IMAGE 4: The progression of active material in Nema Premium 4 motors

| IMAGE 5: Comparison chart of current behavior over time for NEMA Premium 4 and NEMA premium efficient motors
How to Prepare for the Changes
Facility managers, design engineers and planning engineers should consult with motor manufacturers and pump manufacturers who supply motors with their pumps to ensure the pump systems they are maintaining, designing or upgrading will be compatible with the new requirements. Project leaders in planning and design stages need to be aware of the new DOE changes now so they can be knowledgeable about selecting motors and supporting electrical equipment that will meet the new criteria.
Facility managers maintaining current pump systems can begin to examine their installations and plan ahead for the electrical system upgrades that may be needed when their current NEMA Premium Efficient motor needs to be replaced. In cases where it may be costly to upgrade the electrical system, they may want to purchase a NEMA Premium efficient motor now to keep on hand as a replacement for use when the currently installed motor is sent to an Electrical Apparatus Service Association shop for repair.
Jeff Goldberg is market manager at Nidec Motor Corporation/U.S. MOTORS. For more information, visit acim.nidec.com/en/motors/usmotors.